Large stainless steel exhaust silencer on a galvanised support frame above a generator set in a plantroom

Services

Generator exhausts and silencers. Designed, supplied, installed, tested.

For M&E contractors, main contractors and consultants with standby generators, CHP or diesel fire pumps to exhaust.

  • Supply only
  • Install only
  • Supply and install

Need a silencer sized to a noise limit? Exhaust silencers

  • 57Generator and engine exhaust jobs our team has delivered, on our project map
  • 28Of them written up as case studies
  • 24 hoursTo a price, from drawings or survey information
  • 7 daysTo a survey, normally within a week of order
  • 60 minutesTo calculations and CAD drawings after survey

Job-specific RAMS normally the same day. 2 to 4 weeks from order to install, faster when it is urgent. How we work

Case studies

Generator jobs we have done.

Real jobs with photos, flagship jobs first. The row moves on its own: hover, touch or tab into it to stop it, or swipe it along.

All projects

What's in the package

Plantroom to terminal, one package.

The route, the silencer, the supports and the terminal, sized against the engine data and the acoustic target.

Supply only, install only, or supply and install.

Commercial and industrial only. We do the flue, chimney and exhaust, not the boiler or generator itself, and not domestic work.

  • Route design, plantroom to terminal
  • Silencer sizing and selection
  • Standby, CHP and fire pump sets
  • Supports, frames and brackets
  • Flexible connections and test tees
  • Insulation and cladding
  • Testing and certificate
  • O&M pack at handover

To price it, send what you have.

Drawings, photos or an outline is enough. These help:

  • Engine or generatorMake, model, how many
  • OutputkW or kVA each
  • Outlet sizeAt the engine
  • Rough routeUp and across, in metres
  • New or existingAnd what is there now
  • TerminationRoof, wall or stack
  • SiteTown or postcode

Noise

Silencers sized to your noise limit.

Give us the limit in dB(A) and where it applies: a set distance, the nearest home or the site boundary. We work back from it to the silencer the exhaust needs, then check the silencer's back pressure against the engine's limit.

No limit set yet? We size to a grade instead.

Silencer grades and the noise reduction each one typically gives
GradeTypical reduction
Industrial12 to 18 dB(A)
Semi residentialBetween industrial and residential
Residential18 to 25 dB(A)
Critical25 to 35 dB(A)
Hospital32 to 42 dB(A)

Grade names aren't a fixed standard, so these are typical ranges, not promises. What a silencer really takes off depends on its size and the engine, so we check it against your limit on every job.

What we need to size it

  • The engine datasheet: exhaust flow, exhaust temperature and the maximum back pressure
  • The exhaust outlet size
  • The noise limit and where it applies, or the grade
  • The distance from the exhaust outlet to that point

We don't guess the datasheet figures. If one is missing, we ask.

Fire pumps

Fire pump and sprinkler pump engine exhausts.

A diesel fire pump or sprinkler pump engine needs an exhaust like any other engine: a route out of the pump room, a silencer, supports and a terminal. We design and install them the same way as a standby generator exhaust, sized against the engine data.

At Motel One on Blackfriars Road in London the stainless exhaust for the diesel sprinkler pump engine rises from the engine through a flexible connection, into a silencer, and on up to an elbow at high level, held on strut channel supports. The client got a photo progress report each day we were on site.

Motel One sprinkler pump exhaust

Stainless exhaust flue and silencer rising from a fire pump engine
Sprinkler pump engine exhaust, London.

The engineering

Drawn before it is built.

Real Grün drawings. Calculations and CAD drawings normally back within 60 minutes of survey. Pick a number to see where it is on the drawing.

Isometric drawing of four generator sets with four silencers and four twin wall stacks through the roof
Salmon farm, Applecross. First iteration isometric, not to scale, roof and wall cut away.

Design and calculations

Our drawings

Drawn by us, for real jobs.

Real general arrangement drawings from generator and engine exhaust jobs. Calculations and CAD drawings normally back within 60 minutes of survey. Pick one to see it full size.

Client names, site addresses and title block details are blanked out.

On site

Silencers, stacks and terminals.

A Grün project manager on site and daily photo progress reports on every job.

  • Four stainless generator exhaust runs with silencers at high level above switchgear Four silencer runs, Applecross
  • Generator exhaust silencer hung beneath cable tray on threaded rods and channel Silencer at high level, London
  • Generator exhaust stack rising from a silencer inside a galvanised steel support frame Silencer and stack frame, Hillingdon
  • Large stainless generator exhaust run across a roof on low steel supports beside roof plant Roof run to the stack, King's Cross
  • Generator exhaust flue fixed up the side of a clad data centre, ending in a bent terminal Exhaust up the cladding, Worcester
  • Tall generator exhaust held in a cross-braced steel frame above a generator enclosure Braced stack over the generator, Coventry
  • Stainless generator exhaust terminal on a rooftop with the City of London skyline behind Roof terminal, Shoreditch

Common questions

Asked most on generator jobs.

Anything else, call 01395 201950 or email [email protected].

  • Do you do generator exhausts?

    Yes. We design and install the exhaust route, silencers and supports together, with silencer sizing calculations and design notes.
  • What do you need to price a job?

    Drawings, photos or an outline is enough to start. It helps to have: • appliance type and how many • output in kW or kVA • spigot or outlet sizes • rough vertical and horizontal lengths • new flue or existing chimney • termination and site location We price from that or arrange a survey.
  • How quickly do you send a price?

    We normally send a price within 24 hours of getting drawings or survey information.
  • What testing do you do?

    Pressure testing with a test report, smoke testing and CCTV surveys. Each installation includes the testing agreed for the project, with test reports and a certificate of conformity where applicable.
  • Do you do supply only?

    Yes. We do supply only, install only, or supply and install.
  • What warranty do you give?

    12 months on our workmanship, plus the manufacturer’s warranty on the materials.
  • What is your lead time?

    Normally 2 to 4 weeks from order to install. We can speed this up for urgent jobs.

Send drawings. Get a price.

Send the engine data and the route. A price normally comes back within 24 hours.

Free survey

Want us to come and look?

Free for commercial and industrial projects. We’ll call to confirm the details and the date before anything is booked.